vertiv

Vertiv UPS GXT5-1500IRT On Line UPS Rack/Tower 1500VA/1500W

(No reviews yet) Write a Review
SKU:
UP4509
Condition:
New
Availability:
Normally Ships Same Day If Ordered Before 2pm.
$3,289.44

Description

True on-line double conversion 1500VA/1500W UPS system, optional extended battery runtime (UP4532). Rack or tower configuration. Includes rack mount kit. Communications Card RDU101. Replacement batteries 4x UP7905

Features
Top-level on-line double conversion UPS for mission-critical applications
Unity output power factor
LCD multi-language color display (gravity sensing)
On-line (VFI) mode efficiency up to 94% at full load
Active ECO mode efficiency up to 98%
Energy Star® 2.0 certified
Controllable and programmable output sockets
Integrated solution with batteries and electronics
External battery cabinets auto-detection
Operates at full power up to 40ºC (up to 50ºC with derating) Intelligent Communication ready
Safety Agency Approved Category B IEC 61000-4-5 Surges/Lightning protection capability)
Warranty
36 Month Return to Base Warranty

Specifications
Rating 750VA/750W
Input Rated Voltage 230VAC
Rated Frequency 50/60Hz
Frequency Range 40 to 70 Hz
Power Factor ≥0.99
Output Nominal Voltage 200/208/220/230/240 VAC
Waveform Sine wave
Inverter Overload Capability >200% minimum 250 mS, 150 to 200% for 2 seconds; 125 to 150% for 50 seconds; 105 to 125% for 60 seconds
Efficiency in Online Mode Up to 93%
Inverter Bypass Up to 98%
Output Receptacles 8x EN60320/C13
Internal Battery Rated Voltage 48Vdc
Charger Current Nominal 2.2 A; Maximum 8A
Type Valve-regulated, non-spillable, lead acid
Quantity x V x Rating 4 x 12V x 9.0Ah
End Cell Voltage 1.67 V/cell (discharge voltage per cell will be from 1.67 Vdc to 1.90 Vdc, can be selected by PARAMSET)
Floating Voltage Equalize charge: 2.35 V/cell; Float charge: 2.27 V/cell
Battery Voltage Range 40 Vdc to 56.4 Vdc
Internal Battery Backup Time (Approximate) 10% Load Capacity: 88 mins 20% Load Capacity: 42.5 mins 30% Load Capacity: 25.5 mins 40% Load Capacity: 17.5 mins 50% Load Capacity: 13 mins 60% Load Capacity: 10.5 mins 70% Load Capacity: 8.5 mins 80% Load Capacity: 7 mins 90% Load Capacity: 6 mins 100% Load Capacity: 5 mins
General Operating Temperature, °C Full power up to 40 ºC (up to 50 ºC with derating)
Storage Temperature, °C - 15 to + 40
Relative Humidity 0 to 95% non-condensing
Operating Elevation Up to 3,000 m at 25°C without derating
Audible Noise <46 dBA, at 1 meter from sides, <43 dBA, at 1 meter from rear
Safety IEC62040-1:2008 version, GS mark; CE: UL1778 5th Edition and CSA 22.2 No 107.1
EMI/EMC/C-Tick EMC EN 62040-2:2006; EN 61000-3-3:2013; EN 61000-3-3:2013
Transportation ISTA Procedure 1 A
Surge Immunity ANSI C62.41 Category B IEC 61000-4-5 Surges/Lighting
Dimensions (mm) 470 (w) x 430 (d) x 85 (h)
Weight 21.0kg